Preview

Power engineering: research, equipment, technology

Advanced search

Calculation the current carrying capacity of the new generation overhead lines conductors

https://doi.org/10.30724/1998-9903-2020-22-4-3-15

Abstract

Currently, there is an increase in power flows along power lines. An important task for the development of the power grid complex is to increase the current-carrying capacity of existing power lines. The use of advanced conductors has become a successful technical solution for this purpose. "New generation conductors" are modern conductors that have advanced mechanical and electrical properties and characteristics. Thus, it has become important to have information about the maximum operation temperature and current limits of the overhead line with new conductors. The approximate current-carrying capacity in Amperes is the value of current at which the conductor temperature reaches its maximum permissible value. It determines the maximum current load of overhead power lines. For traditional steelaluminum conductors, there are several methodological approaches to determining the maximum current load. This fact complicates the definition of an approach to calculating the current carrying capacity for advanced conductors. Nevertheless, the general basis of all methodological approaches is the thermal balance of the conductor. The purpose of this article is to assess the possibility of adapting the method of calculating the approximate currentcarrying capacity of traditional conductors to the calculation of advanced conductors. The article deals with advanced conductors of various brands of comparable cross-section with the classic ACSR 240/39. This work provides information about the selected conductors, their characteristics and design features. The paper shows a mathematical model for calculating the approximate current-carrying capacity of a conductor and shows calculating results for selected conductors. According to the results of analysis and calculations, the adaptation of the presented mathematical model is possible if we refine its parameters and coefficients.

About the Authors

A. O. Varygina
Amur State University
Russian Federation

Aleksandra O. Varygina

Blagoveshchensk



N. V. Savina
Amur State University
Russian Federation

Natalya V. Savina

Blagoveshchensk



References

1. Fedorov NA. Provoda novogo pokoleniya i voprosy nadezhnosti LEP. Materialy mezhdunarodnoi nauchno-prakticheskoi konferentsii "Rabota sistem elektrosnabzheniya v usloviyakh gololedno-vetrovykh nagruzok"; 19 Oct 2016; Ufa, Russia. Ufa: Publ. Ufa State Aviation Technical University (USATU), 2016. pp. 42-49.

2. Li Z, Zhao , Yang B. Analysis on application of new-type aluminum conductor composite core (ACCC) in power transmission line. 2017 EPTC Power Transmission and Transformation Technology Conference; 15-16 March 2017; Chongqing, China. 2017. pp.1-6. doi: 10.1049/cp.2017.0548.

3. High performance overhead line conductors to upgrade your system. File Library of Nexans. Available at: https://www.nexans.ru/eservice/Russiaru_RU/fileLibrary/Download_540306702/Corporate/files/Brochure_Overhead_Lines_2016BD.pdf. Accessed: 24 May 2020.

4. ACCC High Performance Conductors for a Low Carbon World // Brochure. Available at: https://s3.amazonaws.com/ctc-media/wp-content/uploads/20190420110633/Brochure.pdf Accessed: 24 May 2020.

5. IEEE Standard for Calculating the Current-Temperature Relationship of Bare Overhead Conductors, IEEE Std 738–2012 (Revision of IEEE Std 738–2006 – Incorporates IEEE Std 738–2012 Cor 1–2013). 2013. P. 72.

6. CIGRE P. Guide for Thermal Rating Calculations of Overhead Lines. Technical Brochure. 2014.V. 601.

7. Staszewski L, Rebizant W. The differences between IEEE and CIGRE heat balance concepts for line ampacity considerations. Modern Electric Power Systems (MEPS): Proceedings of the International Symposium. 2010. pp. 1-4.

8. Bangay J, Coleman M, Batten R. Comparison of IEEE and CIGRE methods for predicting thermal behaviour of powerlines and their relevance to distribution networks. 2015 IEEE Eindhoven PowerTech. 2015. pp. 1-5.

9. Rahman SA and Kopsidas K. Impact of Simplified Convection Model in Overhead Lines Thermal Rating Calculation Methods. 2018 IEEE/PES Transmission and Distribution Conference and Exposition (T&D). 2018. pp. 1-9.

10. Benato R, Caldon R, Chiarelli A, et al. assessment of installing innovative conductors in overhead lines. 2019 AEIT International Annual Conference (AEIT), Florence; Italy. 2019. pp. 1-6. doi: 10.23919/AEIT.2019.8893409.

11. Kenge AV, Dusane SV, Sarkar J. Statistical analysis & comparison of HTLS conductor with conventional ACSR conductor. 2016 International Conference on Electrical, Electronics, and Optimization Techniques (ICEEOT), Chennai; India. 2016. pp. 2955-2959. doi: 10.1109/ICEEOT.2016.7755241.

12. Varygina AO, Savina NV. The Influence of New Functional Properties of Active-Adaptive Electrical Networks on the Correctness of Selection and Verification of Conductor Cross-Sections by Existing Methods. 2018 International Multi-Conference on Industrial Engineering and Modern Technologies (FarEastCon), Vladivostok; Russia. 2018. pp. 1-5. doi: 10.1109/FarEastCon.2018.8602740.

13. Varygina AO, Savina NV. Specification of the Method for Calculating the Long-Term Permissible Current of Overhead Line Conductors. 2020 International Conference on Industrial Engineering, Applications and Manufacturing (ICIEAM); Sochi; Russia. 2020. pp. 1-8. doi: 10.1109/ICIEAM48468.2020.9112085.

14. OHL conductors with a composite core of the ACCC brand. Available at: https://simross.ru/files/35863/%D0%9B%D0%B0%D0%BC%D0%B8%D1%84%D0%B8%D0%BB2014%20%20ACCC_%D0%BF%D1%80.pdf. Accessed: 24 May 2020.

15. Guide for selection of weather parameters for bare overhead conductor ratings // CIGRE WG B2.12. 2006.

16. Vasyura YuF, Glazyrin MA, Pleshkova TA, et al. Otsenka ekonomicheskoi tselesoobraznosti stroitel'stva vysokovol'tnykh linii elektroperedachi s primeneniem provodov novogo pokoleniya. Izvestiya vuzov. Elektromekhanika. 2014;3:71-74.

17. Vikharev AP, Vil'ner AV. Issledovanie kharakteristik koronnogo razryada dlya kompaktirovannykh provodov AERO-Z. Sbornik materialov Vserossiiskoi ezhegodnoi nauchnoprakticheskoi konferentsii «Obshchestvo, nauka, innovatsii» (NPK-2013); 15-16 Apr 2013; Kirov, Russia. Kirov Publ. Vyatka State University, 2013. pp. 2087-2091.


Review

For citations:


Varygina A.O., Savina N.V. Calculation the current carrying capacity of the new generation overhead lines conductors. Power engineering: research, equipment, technology. 2020;22(4):3-15. (In Russ.) https://doi.org/10.30724/1998-9903-2020-22-4-3-15

Views: 916


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1998-9903 (Print)
ISSN 2658-5456 (Online)