Preview

Power engineering: research, equipment, technology

Advanced search

Research of the operation of an autonomous electrical complex with a combined composition of backup power sources

https://doi.org/10.30724/1998-9903-2022-24-4-90-104

Abstract

THE PURPOSE. To analyze scientific and technical information and practical experience of the functioning of autonomous electrical complexes with asynchronous electric motors in the composition. To develop a mathematical model of an autonomous electrical complex of a drilling rig with the presence of an active rectifier, an inverter with pulse-width control signals, as well as combined backup power sources – a battery and a diesel generator set. To establish the influence and expediency of using a combined composition of backup power sources on reliable operation and the possibility of overcoming the voltage failure caused by a sharp increase in load in the steady-state operation of an autonomous electrical complex. METHODS. For the successful fulfillment of the tasks set, this study applied the methods of mathematical modeling of power supply systems, methods of simulation modeling, the theories of automatic control, automated electric drive, and electrical circuits. Also, in research used the MATLAB software package with the built-in Simulink graphic modeling environment to create a mathematical computer model and to process the data obtained analytically. RESULTS. The article describes the relevance of the research topic. The study provides criteria for choosing the composition of backup power sources. Mathematical and simulation models of an autonomous ETC have been developed according to the “power source-frequency converter-industrial load” scheme, taking into account the influence of a non-linear load on the specified power quality indicators. The study has developed the structure of an autonomous electrical complex with a combined composition of backup power sources, which allows to overcome the voltage drop in the network caused by a sharp load surge, while ensuring the required indicators of electricity quality. CONCLUSIONS. The use of a rechargeable battery makes it possible to increase the overload threshold of the main diesel generator set regulated by GOST R 53987-2010 from 30% to 60%, as well as to ensure reliable connection of a backup diesel generator set without interrupting technological processes.

About the Authors

S. S. Chervonchenko
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Sergey S. Chervonchenko

St. Petersburg



V. Ya. Frolov
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Vladimir Ya. Frolov

St. Petersburg



References

1. Ivanova IYu, Tuguzova TF, Popov S.P. Razvitie maloi energetiki na severo-vostoke Rossii: problemy, effektivnost', prioritety. Trudy Mezhdunarodnoi nauchno-prakticheskoi konferentsii «Malaya energetika – 2006», 21-24 noyabrya 2006, Moskva. M.: OAO «Malaya energetika», 2006: 370.

2. Tan Y, Meegahapola L, Muttaqi K M. A review of technical challenges in planning and operation of remote area power supply systems. Renewable and Sustainable Energy Reviews. 2014. V.38. pp. 876–889.

3. Bashmakov IA. Povyshenie effektivnosti energosnabzheniya v severnykh regionakh Rossii. Energosberezhenie. 2017; 2:46-53.

4. Elistratov VV. Energeticheskoe snabzhenie izolirovannykh territorii Rossii. Akademiya energetiki. 2015; 4(66):26-33.

5. Mazidi P, Sanz Bobi M A. Strategic maintenance scheduling in an islanded microgrid with distributed energy resources. Electric Power Systems Research. 2017. V.148. pp. 171-182.

6. Cheremisin VV. Issledovanie i postroenie sutochnykh grafikov aktivnykh nagruzok na shinakh podstantsii. Proryvnye nauchnye issledovaniya kak dvigatel' nauki. Ufa: OOO «Agentstvo mezhdunarodnykh issledovanii». 2017:214-216.

7. Akbari K, Rahmani E, Abbasi A, et al. Optimal placement of distributed generation in radial networks considering reliability and cost indices. Journal of Intelligent and Fuzzy Systems. 2016. V.30. pp.1077-1086.

8. Dmitrienko VN, Lukutin BV. Vybor moshchnosti generiruyushchego oborudovaniya avtonomnoi solnechno-dizel'noi elektrostantsii megavattnogo klassa. Fundamental'nye issledovaniya. 2015;4: 61-66.

9. Ma L, Zhou Q. Voltage Dip Evaluation Index Based on Voltage Dip Matrix. 2017 4th International Conference on Information Science and Control Engineering (ICISCE), 2017, pp. 1327-1330, doi: 10.1109/ICISCE.2017.276.

10. Chervonchenko SS, Frolov VYA. Analysis of the voltage fall of a drilling rig connected to a local energy network. VII International Scientific and Practical Conference “Innovations and Prospects for the Development of Mining Engineering and Electromechanics: IPDME-2020. St. Petersburg Mining University. 2020; 630-634.

11. Bagheri A, Bollen MHJ, Gu IYH. Improved characterization of multi-stage voltage dips based on the space phasor model. Electric Power Systems Research. 2018. (154). pp. 319–328.

12. Chervonchenko S.S., Frolov V.YA. Analysis of the voltage drop of a drilling rig connected to a local energy network. Journal of Physics: Conference Series. 2021. №1753.

13. Besselmann TJ, Cortinovis A, Van de Moortel S, et al. Increasing the Robustness of Large Electric Driven Compressor Systems During Voltage Dips. IEEE Transactions on Industry Applications, V. 54. no. 2, pp. 1460-1468, March-April 2018, doi: 10.1109/TIA.2017.2781638.

14. Kadu AD, Debre P, Juneja R, et al. Application of STATCOM for harmonic mitigation and power factor improvement using direct current control technique. 2017 Second International Conference on Electrical, Computer and Communication Technologies (ICECCT), 2017, pp. 1-4, doi: 10.1109/ICECCT.2017.8118013.

15. Katic VA, Stanisavljevic AM. Novel voltage dip detection algorithm using harmonics in the dip’s transient stage. IECON 2017. 43rd Annual Conference of the IEEE Industrial Electronics Society, 2017, pp. 351-356, doi: 10.1109/IECON.2017.8216063.

16. Ngom I, Member S, Badara A, et al. An Improved Control for DC-Link Fluctuation during Voltage Dip based on DFIG. 2018 9th International Renewable Energy Congress (IREC). 2018, pp. 1-6, doi: 10.1109/IREC.2018.8362458.