Improved method for vibration control of the technical condition of a power transformer based on fractal analysis of the amplitude-time characteristics
https://doi.org/10.30724/1998-9903-2023-25-2-124-136
Abstract
The purpose of this work is to improve the method of vibration control of a power transformer through the use offractal analysis of the amplitude-time signal.
Fractal analysis of the amplitude-time characteristics will allow to quantify the degree of «indentation» of the vibration signal of the transformer associated with a defect. For a quantitative assessment, the fractal analysis coefficient (FAC) was introduced based on the determination of the fractal dimension by the Hausdorff-Besikovich method. To test the developed method, a non-contact laser measuring and diagnostic complex (LCMC) with developed software based on LabVIEW, ImageJ and Python was used. Experimental studies of the transformer TSZ 16 were carried out using the developed method and LCIK. The CFA of the windings and magnetic circuit of the transformer under study, the level of technical condition for the controlled elements of the transformer are determined.
METHODS. The improved method of control makes it possible to increase the accuracy of control of a power transformer during its operation under voltage, which makes it possible to switch from a planned system of transformer repairs to a system for taking repairs according to the current technical condition.
RESULTS. The improved method of vibration control was tested using the developed non contact LCIK, the level of technical condition of the power transformer under voltage was determined.
CONCLUSION. An improved method of vibration control makes it possible to determine the level of technical condition of an energized power transformer with the possibility of automatically obtaining a decision on the technical condition, as well as to use statistical methods for processing and analyzing the signals received from the transformer.
About the Authors
V. R. BasenkoRussian Federation
Vasily R. Basenko
Kazan
I. V. Ivshin
Russian Federation
Igor V. Ivshin
Kazan
O. V. Vladimirov
Russian Federation
Oleg V. Vladimirov
Kazan
M. F. Nizamiev
Russian Federation
Marat F. Nizamiev
Kazan
References
1. Basenko V. R., et al. 3D model of a power transformer for the study of its technical condition by vibration parameters. NEWS OF HIGHER EDUCATIONAL INSTITUTIONS. ENERGY PROBLEMS. 2022; 24 (3): 130-143. doi: 10.30724/1998-9903-2022-24-3-130-143
2. Basenko V. R. Diagnostics of transformers of electrotechnical complexes using non contact laser vibrometers / Nizamiyev M. F., Basenko V. R., Ivshin I. V., Vladimirov O. V. NEWS OF HIGHER EDUCATIONAL INSTITUTIONS. ENERGY PROBLEMS. 2022; 24 (5); 97-109. doi: 10.30724/1998-9903-2022-24-5-97-109
3. Basenko V. R., Vladimirov O. V., Ivshin I. V., et al. Non-contact laser control and measuring complex for determining the level of pressing of windings and magnetic circuit of a power transformer. News of higher educational institutions. ENERGY PROBLEMS. 2021; 23 (3): 155-168.
4. Basenko V. R., Nizamiyev M. F. Analysis of vibration signals of a power transformer using a laser measuring and diagnostic complex. ENERGY-2020 - Fifteenth All-Russian (seventh international) scientific and technical conference of students, graduate students and young scientists. 2020. Collection of conference materials, V. No. 3. P. 26.
5. Gavrilenko A. V., Dolin A. P. Quality control system for pressing the windings and steel of transformers by measuring vibration, monitoring the state of oil pumps. Dimrus - Perm: 2015. - P. 60.
6. Nizamiev M. F., Ivshin I. V. Control of the technical condition of electrical equipment. Energy security. Collection of scientific articles of the III International Congress. 2020. P. 297-300
7. Nizamiev M. F., Ivshin I. V., Maksimov V. V., et al. Measuring and diagnostic complex for monitoring the technical condition of electrical equipment. Electrica 2015. P. 18-25
8. Lazarev I. V. Axial forces in the elements of the active part of a power transformer when pressing windings, changing the temperature and moisture content of insulating materials. Dynamics and Strength of Machines. 2014. P. 12-18
9. Ivshin I. V., Nizamiev M. F., Vladimirov O. V., Dolomanyk L. V. Vibration Method for Monitoring the Technical Condition of Support-Rod Insulators Using Non-Contact Laser Vibrometry Methods / 14<sup>th</sup> International Scientific Technical Conference on Actual Problems of Electronic Instrument Engineering (APEIE) - 44894 Proceedings. V. l, Pt 5, Novosibirsk 2018. P. 320-325.
10. Ivshin I. V., Nizamiev M. F., Vladimirov O. V., et al. The Method of Non-Contact Vibration Control of Energy Device Detail State Based on the Use of Informativ Frequencies of Own Vibrations Related to Certain Types of Defects / Ad Alta. Journal of Interdisciplinary Research, Volum 8, Issue 1, Special Issue III. 2018. P. 322-33
11. Basenko V. R., Nizamiev M. F. Analysis of vibration signals of a power transformer using a laser measuring and diagnostic complex. ENERGY-2020. 2020. P. 26.
12. Rybakov L. M. Methods and methods for assessing the state of power transformers during operation. Bulletin of the Chuvash State Agricultural Academy., 2018; 2: 108-111
13. Nizamiev M. F. Analysis of methods for studying the vibroacoustic characteristics of parts of complex shape and technical means of processing signals of complex shape. 2014; 1: 151-152.
14. Nguyen Tien, Gilfanov K. Kh. Thermal modeling of the TM-160/10 oil-filled power transformer. Izvestiya vuzov. Energy Problems. 2019; 5: 141-151 Kazan: KSPEU.
15. Kurtz С., Ford G., Vainberg М., et al. Managing aged transformers. Transmission & Distribution World. 2005, July. P. 36-45.
16. Metwally I. A. Failures, monitoring, and new trends of power transformers // IEEE potentials. - 2011, May / June. P. 36-43.
17. Theil G. Parameter evaluation for extended Markov models applied to condition- and reliability-centered maintenance planning strategies // Proc. 9<sup>th</sup> Int. Conf. on Probab. Methods Applied to Power Syst., KTH, Stockholm, Sweden. 2006.
18. Gracheva E. l., O. V. Naumov, E. A. Fedotov. Influence of the load capacity of power transformers on their operational characteristics. Izvestiya vuzov. Energy Problems. 2017; 7-8: 71-77. Kazan: KSPEU.
19. Mustafin R. G., Yarysh R. F. Differential method for detecting turn short circuits in a three-phase transformer. Izvestiya vuzov. Energy Problems. 2020; 3: 78-89. Kazan: KSPEU.
20. Order of the Ministry of Energy of the Russian Federation dated July 26, 2017. No. 676 «On approval of the methodology for assessing the technical condition of the main technological equipment and transmission lines of power plants and electrical networks».
Review
For citations:
Basenko V.R., Ivshin I.V., Vladimirov O.V., Nizamiev M.F. Improved method for vibration control of the technical condition of a power transformer based on fractal analysis of the amplitude-time characteristics. Power engineering: research, equipment, technology. 2023;25(2):124-136. (In Russ.) https://doi.org/10.30724/1998-9903-2023-25-2-124-136