Preview

Power engineering: research, equipment, technology

Advanced search

Peducing the frequency of switching overvoltage in generator networks

https://doi.org/10.30724/1998-9903-2024-26-3-96-107

Abstract

THE PURPOSE of the study is to study the problem of switching overvoltages in 10 kV generator networks. Using the Matlab Simulink package, create a model of common auxiliaries of a 10/0.4 kV power station, calculate the overvoltage at different sections of the current, evaluate the effect of vacuum switches on each other, evaluate the effectiveness of nonlinear overstrain limiters, with parallel switching.

THE SCIENTIFIC SIGNIFICANCE consists in obtaining a method for calculating transients with simultaneous switching of several switches. THE PRACTICAL SIGNIFICANCE lies in the possibility of using the resulting model for a more accurate selection of protective equipment.

METHODS. To create a model of common auxiliaries of 10/0.4 kV and the calculations of transition processes, it used a Matlab Simulink package. RESULTS. The article discusses switching overvoltages in their own needs of 10/0.4 kV. The influence of parallel switching of vacuum circuit breakers on the increase in the multiplicity of overvoltages is estimated. The influence of the specific energy intensity of nonlinear surge limiters on the multiplicity of overvoltages was also evaluated.

CONCLUSION. This model showed that the parallel switching of two vacuum circuit breakers can increase the frequency of overvoltage by 20-40 %, which can lead to an increase in wear of both insulation of the protected equipment and the probability of re-breakdown in a vacuum chamber. Moreover, the higher the current cut, the higher the increase in the frequency of the overstrain, the multiplicity will also increase if the shutdown time between the switches is reduced. The main means of protection against switching overvoltages is a non -linear overstrain limiter, but when they are selected, the nominal working voltage is primarily taken into account, which leads to the fact that the increase in the frequency of overstrain from parallel switching can level the effectiveness of a nonlinear limiter.

About the Authors

R. A. Belsky
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Rodion A. Belsky

Saint Petersburg



V. Y. Frolov
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Frolov Y. Vladimir

Saint Petersburg



R. I. Zhiligotov
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Zhiligotov I. Ruslan

Saint Petersburg



E. P. Safonov
Peter the Great St. Petersburg Polytechnic University
Russian Federation

Safonov P. Evgenii

Saint Petersburg



References

1. Evdokunin GA, Tiler G. Modern vacuum switching equipment for medium voltage networks (technical advantages and operational characteristics). 2nd ed. SPb: Publishing house Tertsiya; 2006. (In Russ).

2. Safonov E.P, Frolov V.Ya. Features of fault transient's in generator network of powerful electric power stations // Proceedings of the higher educational institutions. ENERGY SECTOR PROBLEMS. 2021. 23(1):105-118. (In Russ). DOI:10.30724/1998-9903-2021-23-1-105-118

3. Chervonchenko S.S, Frolov V.Ya. Research of the operation of an autonomous electrical complex with a combined composition of backup power sources // Proceedings of the higher educational institutions. ENERGY SECTOR PROBLEMS. 2022. 24(4):90-104. (In Russ). DOI:10.30724/1998-9903-2022-24-4-90-10

4. Pertsev A.A, Belkin G.S. Switching processes in vacuum circuit breakers with parallel connection of arc extinguishing chambers // Elektrotekhnika. 2022. (4):39. (In Russ).

5. Khalilov F.Kh. Protection of 6-35 kV networks from overvoltage. SPb: Energoatomizdat. 2002. (In Russ).

6. Abdulahovic. T, Thiringer T. Vacuum Circuit Breaker Parameter Calculation and Modelling for Power System Transient Studies. Discharges and Electrical Insulation in Vacuum (ISDEIV). 2010; 32 (3): 1165 - 1172. doi: 10.1109/TPWRD.2014.2357993

7. Buyung M, Satyagraha K. Application of Surge Arrester on Vacuum Circuit Breaker: Proceedings of the 2012 Asia-Pacific Power and Energy Engineering Conference, 27-29 March 2012; Shanghai, China; 2012. doi: 10.1109/APPEEC.2012.6307348

8. Adam'yan Yu.E, Bocharov Yu.N, Krivosheev S.I. Dependence of the level of overvoltage of surge arrester of different voltage classes on the parameters of grounding devices. Experiment and simulation. Trudy Kol'skogo nauchnogo tsentra RAN. 2016; 5-13(39):29. (In Russ).

9. Wróblewski Z, Budzisz J. Overvoltage and overcurrent in a capacity circuit generated by a vacuum switch: Proceedings of the 2010 9th International Conference on Environment and Electrical Engineering; 16-19 May 2010; Prague, Czech Republic; 2010. doi: 10.1109/EEEIC.2010.5489980

10. Huang Z, Tan W, Mao Q, et al. Controlled Breaking Strategy of Shunt Reactor Based on Fast Vacuum Switch: Proceedings of the 2019 5th International Conference on Electric Power Equipment - Switching Technology (ICEPE-ST); 13-16 October 2019; Kitakyushu, Japan, 2019; pp. 698-701. doi: 10.1109/ICEPE-ST.2019.8928747.

11. Xin Y. Development of Improved Suppression Measures Against Reignition Overvoltages Caused by Vacuum Circuit Breakers in Offshore Wind Farms //IEEE Transactions on Power Delivery. 2022; 21(1):517-527. doi: 10.1109/TPWRD.2021.3064306.

12. Asadi Q, Qasemi M, Amini A, et al. Minimizing Overvoltages on Medium Voltage VCBs Due to Shunt Reactor Switching: Proceedings of the 2020 15th International Conference on Protection and Automation of Power Systems; 30-31 December 2020; Shiraz, Iran; 2020. pp. 25-29. doi: 10.1109/IPAPS52181.2020.9375585.

13. Liu G, Guo F, Yuan K. Overvoltage Simulation and Analysis of Switching-off Shunt Reactor with 12kV Vacuum Circuit Breaker: Proceedings of the 2020 5th Asia Conference on Power and Electrical Engineering; 04-07 June 2020; Chengdu, China, 2020. pp. 1610-1614. doi: 10.1109/ACPEE48638.2020.9136172.

14. Su X, Luo J, Xu B, et al. Research on parallel mean flow technology of high-voltage vacuum circuit breaker: Proceedings of 2022 IEEE International Conference on Electrical Engineering, Big Data and Algorithms (EEBDA); Changchun, China; 2022. pp. 146-149, doi: 10.1109/EEBDA53927.2022.9744928.

15. Zhou F, Tang W, Ma Y, et al. Research on Circuit Breaker Switching Model Modified Based on Measured Data Considering Multi Stochastic Factors: Proceedings of 2020 IEEE International Conference on High Voltage Engineering and Application; Beijing, China; 2020. pp. 1-4, doi:10.1109/ICHVE49031.2020.9279912.


Review

For citations:


Belsky R.A., Frolov V.Y., Zhiligotov R.I., Safonov E.P. Peducing the frequency of switching overvoltage in generator networks. Power engineering: research, equipment, technology. 2024;26(3):96-107. (In Russ.) https://doi.org/10.30724/1998-9903-2024-26-3-96-107

Views: 132


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1998-9903 (Print)
ISSN 2658-5456 (Online)