Method of calculation of temperature parameters and servic life of cable lines with a voltage of 10 kV
https://doi.org/10.30724/1998-9903-2024-26-4-65-74
Abstract
RELEVANCE. The paper presents a method for calculating the temperature parameters and service life of cable lines (CL) with a voltage of 10 kV for various types of insulation and operating conditions. Dependencies have been developed that are recommended for clarifying the parameters of the CL, taking into account different operating modes. The results of the study can be used for practical application and will contribute to reducing the number of accidents resulting from thermal breakdowns of CL due to incorrect selection of CL parameters.
PURPOSE. To investigate the temperature parameters of 10 kV CL, taking into account various methods of laying them and load factors for the climatic conditions of the Republic of Tatarstan.
METHODS. Methods for calculating the temperature parameters of CL and their service life, methods of statistical data processing, and methods for approximating functions are used. The ELCUT software package is used to visualize the results obtained during calculations. results. The results of calculations of the temperature parameters of 10 kV CL with paper-impregnated insulation (BPI), polyvinyl chloride plastic (PVC) insulation and polyethylene (PE) insulation during their laying in air, in the ground, in the ground in a pipe, taking into account the load coefficients of cable lines, are presented. The results of calculations of the service life of the CL are shown. The values of the optimal load coefficients of the CL are determined to reduce the rate of thermal aging of insulation under various operating conditions. conclusion. The results of the conducted research and calculations can be used to evaluate and select the optimal load of 10 kV CL at the stages of operation and design of power supply systems.
About the Authors
I. I. TsitsonRussian Federation
Ivan I. Tsitson
Kazan
E. Yu. Abdullazyanov
Russian Federation
Edward Yu. Abdullazyanov
Kazan
E. I. Gracheva
Russian Federation
Elena I. Gracheva
Kazan
A. E. Nemirovsky
Russian Federation
Alexander Ye. Nemirovsky
Vologda
S. Valtchev
Russian Federation
Valtchev S.
Portugal
References
1. Gracheva E.I., Muravyov G.G. Investigation of temperature regimes and parameters of cable lines of electrical equipment of power plants // NAUKA. technologies. INNOVATIONS. 2020. T. 4. pp. 151-154.
2. Gracheva E.I., Gorlov A.N., Alimova A.N. Research and assessment of electricity losses in inhouse power supply systems // Bulletin of the Kazan State Energy University. 2019. T. 11. No. 4(44). pp. 22-29.
3. Gracheva E.I., Alimova A.N. Possible errors in the calculation of electricity losses in shop industrial networks // Izvestia of higher educational institutions. ENERGY PROBLEMS. 2018. Vol. 20. No. 11-12. pp. 81-92. DOI:10.30724/1998-9903-2018-20-11-12-81-92.
4. Gracheva E.I., Gizzatullina E.E. Reliability analysis of workshop networks // News of universities. Energy problems. 2003. No. 5-6.
5. Titkov V.V. On the issue of introducing a thermal regime of a three-phase LNG cable line // CABLE-News. 2018. No. 10. pp. 3-10.
6. Kovrigin L. A. Calculation of temperature fields and current load in ANSYS // CABLE-News. 2009. No. 4. pp. 2-6.
7. Gladysheva M.M., Sukhacheva E.K., Khatyushina T.V. Mathematical model of software for an automated system for selecting cable lines of industrial enterprises // SibAK. 2015. No. 12(48). pp. 20-23.
8. Gracheva E.I., Gorlov A.N., Shakurova Z.M., Tabachnikova T.V. Equivalent resistance of industrial electric networks as one of the main characteristics in calculations of electricity losses // INSTRUMENTATION AND AUTOMATED ELECTRIC DRIVE IN THE FUEL AND ENERGY COMPLEX AND HOUSING AND COMMUNAL SERVICES. 2022. pp. 540-544.
9. Korzhov A.V., Sidorov A.I., Tomasheva E.V. The influence of the magnetic field of cables 6-10 kV on their insulation // Electricity. 2009. pp. 46-53.
10. Biryulin V.I., Kudelina D.V., Gorlov A.N. Calculation of the heating temperature of cable insulation taking into account the influence of nearby laid cables // Bulletin of the Kazan State Energy University. 2019. Vol. 11. No. 2 (42). pp. 56-64.
11. Ilyichev N.B., Vermakhovsky A.N. Calculation of the temperature of cable cores in the design of distribution networks // Effective technologies for designing power supply and automation systems. Reorganization of the CSoft Group of companies. CJSC "SiSoft Ivanovo", CJSC "SiSoft". Ivanovo-Moscow, 2012. pp. 22-28.
12. Lebedev D.V., Zaitsev E.S. Calculation of the core temperature of a single-phase high-voltage cable with cross-linked polyethylene insulation in real time // Bulletin of the Ivanovo State Energy University. 2015. No. 4. pp. 11-16.
13. Zalizny D.I., Shirokov O.G. Adaptive mathematical model of thermal processes of a three-core power cable // Bulletin of the Gomel State Technical University named after P.O. Sukhoi. 2014. No. 2 (57). pp. 51-63.
14. R. Gono, S. Rusek, M. And Kratki Z. Leonovich, Reliability analysis of the electric power distribution system, 2011. 10th International Conference on Environment and Electrical Engineering, Rome, Italy, 2011, pp. 1-4, doi identifier: 10.1109/EEEIC.2011.5874842.
15. K. Chen, Yu. Yue, Yu. Tang, Investigation of the method of cabin temperature control on 10 kV railway power lines based on a distributed temperature sensor, Energy 2021, 14 (12), 3705; https://doi.org/10.3390/en14123705.
16. R. Jongen; E. Gulsky; J. Smith, Failures of medium voltage cable connections depending on ambient temperature, CIRED 2009 - 20th International Conference and Exhibition on Power Distribution; doi number: 10.1049/WED.2009.0832.
17. R.A. Jongen; P.H.F. Morshuis; J.J. Smith; A.L.J. Janssen, The influence of ambient temperature on the behavior of cable connections during failure, Annual Report of the Conference on Electrical Insulation and Dielectric Phenomena for 2007; doi identifier: 10.1109/CEIDP.2007.4451520.
18. T.Bragatto; A.Cerretti; L.D'Orazio; F.Massimo Gatta; A.Geri; M.Macchioni, Thermal effects of earth faults on high-voltage connections and cables; energy, 2019, 12(18), 3496; https://doi.org/10.3390/en12183496.
Review
For citations:
Tsitson I.I., Abdullazyanov E.Yu., Gracheva E.I., Nemirovsky A.E., Valtchev S. Method of calculation of temperature parameters and servic life of cable lines with a voltage of 10 kV. Power engineering: research, equipment, technology. 2024;26(4):65-74. (In Russ.) https://doi.org/10.30724/1998-9903-2024-26-4-65-74