Dynamic voltage restorer application in the multi-motor electric drive system of a belt conveyor

https://doi.org/10.30724/1998-9903-2025-27-2-49-62

Abstract

Relevance of this research lies in addressing the issue of the voltage distortions’ negative impact on belt conveyor electric drive systems, caused by irregularities in the voltage waveform of power supply networks at coal mining facilities.

The purpose of this study is to create a mathematical and computer model that demonstrates the effectiveness of using a dynamic voltage restorer (DVR) in a belt conveyor multi-motor electrical drive system powered by an underground electrical network.

Methods. A multi-motor electromechanical system consisting of three BA280S4 low-voltage asynchronous motors with a total power of 330 kW making up the electric drive for the 2L100U-01 mining belt conveyor system is the object of this research. The study of the DVR operation in the electromechanical system under consideration was carried out by computer modeling using the MATLAB/Simulink® software.

Results. Simulation of system operation with the DVR and without it was performed for the following modes: studying the static stability of the system when the grid voltage reduces to 0.5 pu of its nominal value, studying the dynamic stability when the grid voltage fails for up to 8 seconds, the occurrence of non-sinusoidal and asymmetric voltage waveforms for 1-2 seconds. The simulation results confirm that, without the use of a DVR, the operation of the conveyor drive under voltage asymmetry conditions is characterized by multiple torque overloads, and in cases where voltage is reduced to 0.5 pu of the nominal value or is cut off for more than 8 seconds, there is a loss of speed stability. The use of the DVR ensures the restoration of the voltage waveform and the stability of the transient characteristics of drive speed and torque.

Conclusion. The conducted research illustrates that the DVR is an effective way to ensure stable and reliable operation of low-voltage multi-motor electric drives in high-performance coal mining belt conveyor facilities. The introduction of a DVR is reasonably recommended for coal mining enterprises.

About the Authors

D. V. Dzyuin
National University of Oil and Gas «Gubkin University»
Russian Federation

Dmitry V. Dzyuin,

Moscow



G. A. Skopin
National University of Oil and Gas «Gubkin University»
Russian Federation

Georgy A. Skopin,

Moscow



A. N. Komkov
National University of Oil and Gas «Gubkin University»
Russian Federation

Aleksandr N. Komkov,

Moscow



V. V. Dmitrieva
National University of Oil and Gas «Gubkin University»
Russian Federation

Valeria V. Dmitrieva,

Moscow



References

1. Plashchansky LA, Reshetnyak SN, Reshetnyak MY. Improvement of electric energy quality in underground electric networks of highly productive coal mines. Mining Science and Technology (Russia). 2022; 7(1):66–77. (In Russ). DOI: 10.17073/2500-0632-2022-1-66-77

2. Romanova VV, Batukhtin AG, Suslov KV, Khromov SV, Galyatin VА. Comprehensive assessment of factors affecting the operational reliability of low-voltage asynchronous electric motors of a coal mining complex. Power engineering: research, equipment, technology. 2024; 26(5):3-18. (In Russ). DOI: 10.30724/1998-9903-2024-26-5-3-18

3. Kolb A, Pazynich Y, Mirek A, et al. Influence of voltage reserve on the parameters of parallel power active compensators in mining. E3S Web of Conferences. 2020; 201(01024):1-11. DOI: 10.1051/e3sconf/202020101024

4. Sychev YA, Aladin ME, Zimin RY. Multi-function filter compensation devices in composite power supply systems in mining industry. MIAB. Mining Inf. Anal. Bull. 2022; 7:164-179. (In Russ). DOI: 10.25018/0236_1493_2022_7_0_164

5. Sinyavsky O, Savchenko V, Liktey V, et al. Influence of voltage unsymmetry on energy characteristics of belt conveyor. Energy and automation. 2022; 4:1-16. DOI: 10.31548/energiya2022.04.016

6. Romanova VV, Khromov SV, Batukhtin AG, Suslov KV. Analysis of the degree of influence of supply voltage asymmetry on the operational reliability of low-voltage asynchronous electric motors. Power engineering: research, equipment, technology. 2022; 24(4):131-141. (In Russ). DOI:10.30724/1998-9903-2022-24-4-131-141

7. Reutov AA. CHOOSING THE CONVEYOR DRIVE LAYOUT TAKING INTO ACCOUNT UNCERTAIN OPERATING CONDITIONS. Transport engineering. 2024; (3):31-40. (In Russ). DOI: 10.30987/2782-5957-2024-3-31-40

8. Bajda M, Hardygóra M, Marasová D. Energy efficiency of conveyor belts in raw materials industry. Energies. 2022; 15(9):3080. DOI: 10.3390/en15093080

9. Zatsepina VI, Zatsepin EP, Skomorokhov PI. Improving the efficiency of power supply systems through the combined effect of voltage distortion. Power engineering: research, equipment, technology. 2019; 21(5):79-86. (In Russ). DOI: 10.30724/1998-9903-2019-21-5-79-86

10. Fedotov AI, Kuznetcov RV, Fedotov EA, Leuhin AN. Effect of dynamic compensators voltage distortion on the power quality during faults on the electrical networks. Power engineering: research, equipment, technology. 2015; (3-4):36-41. (In Russ.) DOI: 10.30724/1998-9903-2015-0-3-4-36-41

11. Karuppannan A, Mohanaprasaath S. Design of Dynamic Voltage Restorer for Power Quality Improvement. Mediterranean Journal of Basic and Applied Sciences. 2024; 08(2):54-62. DOI: 10.46382/MJBAS.2024.8205

12. Liu A, Wang Y, Zhu Y, et al. Research on power quality improvement system based on dynamic voltage restorer. IET Power Electron. 2024; 17:1399–1410. DOI: 10.1049/pel2.12696

13. Abdelaal AK, Shaheen AM, El-Fergany AA, et al. Sliding mode control based Dynamic Voltage Restorer for Voltage Sag Compensation. Results in Engineering. 2024; 24(102936):1-12. DOI: 10.1016/j.rineng.2024.102936

14. Zahra ST, Khan RU, Ullah MF, et al. Simulation-based analysis of dynamic voltage restorer with sliding mode controller at optimal voltage for power quality enhancement in distribution system. Electrical Engineering & Electromechanics. 2022; 1:64-69. DOI: 10.20998/2074-272X.2022.1.09

15. Dmitrieva VV, Dzyuin DV. Mathematical and computer model of a multi-mass multi-motor electric drive system of a belt conveyor. Mining Equipment and Electromechanics. 2024; 2(172):3-12 (In Russ., abstract in Eng.). DOI: 10.26730/1816-4528-2024-2-3-12

16. Skopin GA. Issledovanie rezhimov raboty dinamicheskogo kompensatora iskazhenii napryazheniya v sisteme elektrosnabzheniya neftepererabatyvayushchego zavoda [Study of the operating modes of a dynamic voltage distortion compensator in the power supply system of an oil refinery]. Novye tekhnologii v gazovoi promyshlennosti: gaz, neft', energetika: XIV Vserossiiskaya konferentsiya molodykh uchenykh, spetsialistov i studentov: tezisy dokladov, Moskva, 14–18 noyabrya 2022 goda. Moscow: Rossiiskii gosudarstvennyi universitet nefti i gaza (natsional'nyi issledovatel'skii universitet) imeni I.M. Gubkina [National University of Oil and Gas «Gubkin University»], 2022. Pp. 669-670. (In Russ.).