Development of an energy model of a data center
https://doi.org/10.30724/1998-9903-2025-27-4-147-156
Abstract
Relevance. Data centers are a specialized facility that is an interconnected system of IT infrastructure, engineering infra-structure, equipment (server and network) and parts of which are located in a building or room connected to external networks, both engineering and telecommunications. Due to the significant heat generation of these systems, there is a need to increase the efficiency of cooling systems through efficient heat recovery.
The purpose. Calculation of the energy balance of a typical data center designed for operation in central Russia.
Methods. The developed energy model of a data center is a mathematical description of all energy processes in a building, including heat transfer processes, the effects of ventilation and air conditioning, the operation of lighting, electrical appliances and other equipment, and the operation of engineering systems.
Results. According to the simulation results, the specific energy consumption was 1,353 kWh/m2, the specific annual cost of energy resources was 8,572.90 rubles/m2. The following key results were obtained: energy consumed by data center modules – 38,399.53 MWh/year; energy consumed by IT equipment – 31,685.20 MWh/year; PUE (it represents the ratio of the total energy consumed by the data center to the energy directly used by the IT equipment) – 1.21.
Conclusion. Data on annual energy consumption, the cost of consumed energy resources and the amount of CO2 released into the atmosphere during the production of energy resources were obtained. A monthly energy consumption chart has been developed by category (heating, cooling, fans, heat recovery, pumps, interior lighting, outlet equipment, servers). In the course of further research, it is planned to consider priority schemes for the utilization of thermal energy of the data center.
References
1. IKS Consulting. Analytical report "Russian market of commercial data centers 2023" [Electronic resource]: The market of commercial data centers in Russia 2023 – Access mode: https://survey.iksconsulting.ru/page30265406.html
2. International Data Corporation. Режим доступа: https://www.idc.com/.
3. GOST R 70139-2022 Data processing centers. Engineering infrastructure. Classification.
4. Stockholm Data Parks [Electronic resource]: Stockholm Data Parks – Access mode: https://stockholmdataparks.com/.
5. Arianna Tofani. A case study on the integration of excess heat from Data Centres in the Stockholm district heating system // TRITA: TRITA-ITM-EX 2022:469, Stockholm, Sweden 2022. p. 56.
6. Cristina Ramos Caceres, Marcus Sandberg, Adolfo Sotoca. Planning data center locations in Swedish municipalities. A comparative case study of Luleå and Stockholm // Cities 150, 2024. p. 22.
7. Tao Lu, Xiaoshu Lü, Matias Remes, Martti Viljanen. Investigation of air management and energy performance in a data center in Finland: Case study // Energy and Buildings 43, 2011. p. 3360–3372.
8. Mikko Wahlroos, Matti Pärssinen, Samuli Rinne, Sanna Syri, Jukka Manner. Future views on waste heat utilization – Case of data centers in Northern Europe // Renewable and Sustainable Energy Reviews 82, 2018. p. 1749–1764.
9. Mikko Wahlroos, Matti Pärssinen, Jukka Manner, Sanna Syri. Utilizing data center waste heat in district heating – Impacts on energy efficiency and prospects for low-temperature district heating networks // Energy 140, 2017. p. 1228–1238.
10. Rasmussen N. Calculation of technical requirements for general cooling in data centers / N. Rasmussen // American Power Conversion Information Technology. – 2003. – № 25. – 9 C.
11. Chayan Nadjahi, Hasna Louahlia, Stéphane Lemasson A review of thermal management and innovative cooling strategies for data center // NORMANDIE UNIV, UNICAEN, LUSAC, 2018. p. 14-28.
12. Ahmed A. Alkurush, Mohamed S. Salem, O. Abdelrehim, A.A. Hegazi. Data centers cooling: A critical review of techniques, challenges, and energy saving solutions // International Journal of Refrigeration 160, 2024. p. 246-262.
13. Suhas V. Patankar. Airflow and cooling in a data center // Journal of Heat Transfer, 2010. p. 17.
14. B. Fakhim, M. Behnia, S.W. Armfield, N. Srinarayana. Cooling solutions in an operational data centre: A case study // Applied Thermal Engineering 31, 2011. p. 2279-2291.
15. Hongjie Lu, Zhongbin Zhang, Liu Yang. A review on airflow distribution and management in data center // Energy & Buildings 179, 2018. p. 265-277.
16. Yu.I. Soluyanov, A. I. Fedotov, A. R. Akhmetshin // Calculation of the correction factor to the normative values of specific electrical loads of apartment buildings in Moscow and the Moscow region // Publications of higher educational institutions. Energy problems. – 2022. – Vol. 24, No. 4. – pp. 142-153. – DOI 10.30724/1998-9903-2022-24-4-142-153.
17. M.S. Ivanitsky // Technological standards and emission indicators of thermal power plants and boiler houses // News of higher educational institutions. Problematic issues. – 2024. – VOL. 26, No. 3. – pp. 3-15. – DOI 10.30724/1998-9903-2024-26-3-3-15.
Review
For citations:
Yudin A.K. Development of an energy model of a data center. Power engineering: research, equipment, technology. 2025;27(4):147-156. (In Russ.) https://doi.org/10.30724/1998-9903-2025-27-4-147-156