Preview

Power engineering: research, equipment, technology

Advanced search

FEATURES OF MONITORING PARTIAL DISCHARGE IN THE STATOR WINDING INSULATION OF TURBINE GENERATORS, INCLUDED IN THE NETWORK

https://doi.org/10.30724/1998-9903-2017-19-3-4-80-88

Abstract

In this paper reports the results of studies of the surveillance of partial discharge (PD) in the stator the turbine generator (TG) TVF-60-2 when its work on the network. Shown that, for a correct interpretation of the measurement results PD in TG, it is necessary to know winding diagram and the order of their location in the stator slots; circuit crossing them in the end-winding and the stress distribution at the bars in the slot and end-winding part of the TG. Consequently, series-connected stator bars potentially different relative to the ground, the conditions of occurrence of PD in each bar in the slot and end-winding part are substantially different and the phase of occurrence of PD becomes ambiguous parameter.

About the Authors

B. A. Ba
Kazan State Power Engineering University
Russian Federation


A. E. Usachev
Kazan State Power Engineering University
Russian Federation


A. Kubarev
Kazan State Power Engineering University
Russian Federation


S. M. Margulis
Kazan State Power Engineering University
Russian Federation


References

1. Hutter W. Partial Discharge Detection in Rotating Electrical Machines//IEEE Electrical Insulation Magazine. -1992. -V.8. - No.3. - pp. 21-32.

2. ГОСТ IEC/TS 60034-27. Машины электрические вращающиеся. Часть 27. Измерения частичного разряда на изоляции статорной обмотки включенных в сеть вращающихся электрических машин М: Изд-во Стандарты. 2015. 55 с.

3. IEC/TS 60034-27. Rotating electrical machines - part 27: off-line partial discharge measurements on the stator winding insulation of rotating electrical machines. 2006-12-01. p 120.

4. Hoof M., Lanz S. PD Diagnostics on Rotating Machines Possibilities and Limitations // Electrical Insulation Conference - Cincinnati, USA. - Oct.1999 - pp. 195-200.

5. Русов В.А. Измерение частичных разрядов в изоляции высоковольтного электрооборудования / В.А. Русов. Екатеринбург: УрГУПС, 2011. 367с.

6. Interpretation of PD results - on-line testing - Version 3.2 Iris QMS 08/10.Ver. 3.2. 2008.

7. Вдовико В.П. Частичные разряды в диагностировании высоковольтного оборудования / В.П. Вдовико - Новосибирск: Наука, 2007. 155 с.

8. GregC. Stone, Edward A. Boulter, Ian Culbert, Hussein Dhirani. Electrical insulation for rotating machines design, Evaluation, Aging, Testing, and Repair / by GregC. Stone[and others]- Canada: IEEE Press Editorial Board,2003.- 390 p.

9. Pemen, August J.M. Detection of partial discharges in stator windings of turbine generators/by August J.M. Pemen. Eindhoven :TechnischeUniversiteit Eindhoven, 2000.- 177 p.

10. A. Pemen,P. Van Der Laan,W. de Leeuw. Propagation of partial discharge signalsin stator windings of turbine generators//IEEE Transactions on Energy Conversion -2006.21(1) pp. 155 -161.


Review

For citations:


Ba B.A., Usachev A.E., Kubarev A., Margulis S.M. FEATURES OF MONITORING PARTIAL DISCHARGE IN THE STATOR WINDING INSULATION OF TURBINE GENERATORS, INCLUDED IN THE NETWORK. Power engineering: research, equipment, technology. 2017;19(3-4):80-88. (In Russ.) https://doi.org/10.30724/1998-9903-2017-19-3-4-80-88

Views: 372


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1998-9903 (Print)
ISSN 2658-5456 (Online)