Preview

Power engineering: research, equipment, technology

Advanced search

INVESTIGATION OF A MIXED-CONVECTIVE HEAT TREATMENT OF SINGLEAIR AIR COOLED EXCHANGERS IN VARIOUS CROSS-STEPS PIPE INSTALLATION

https://doi.org/10.30724/1998-9903-2017-19-11-12-3-11

Abstract

The article presents a study of single-row air-cooled heat exchangers consisting of bimetallic rolling aluminum finned tubes with different transverse steps of their installation, equipped with an additional intensifying device - a suction shaft, of various heights. The methodology of processing the obtained experimental data is analyzed and the Nusselt numbers reliance on Grashof numbers are presented. The physical picture of the air flow structure passing through a single-row horizontal finned beam is analyzed. Because of the analysis, it was concluded that the installation of the exhaust shaft above the beam leads to a significant increase in heat transfer by a factor of 2.5-3.0, but the efficiency of heat transfer depends on the height of the extraction shaft and on the back spacing. In such case the mixed convective heat transfer reliance on back spacing is differed from a character of dependence as compared to free convection heat exchange.

About the Authors

A. B. Sukhotskii
Belarussian state technological university, Minsk
Belarus

PhD (Engineering), Associate Professor, Assistant Professor in the Department of Energy Saving, Hydraulics and Heat Engineering



G. S. Sidorik
Belarussian state technological university, Minsk
Belarus

PhD studentin the Department of Energy Saving, Hydraulics and Heat Engineering



References

1. Kuntysh V. B. Bessonnyj A. N. Examples of calculations of non-standardized effective heat exchangers.SPb.: Nedra, 2000. 300 p.

2. Jaluria, Y., 1980. Natural Convection: Heat and Mass Transfer. Oxford: New York: Pergamon Press, p. 326.

3. Gebhart B.,1973.Natural convection flows and stability. Advances in Heat Transfer, Academic Press. N.Y., Vol. 9, p. 273.

4. Kuntysh V. B., Pozdnyakova A. V., Tretjakov P. A. Generalization of experimental data on free convection for three-row corridor bundles from bimetallic ribbed pipes / Proceedings of the Fifth Russian National Heat Transfer Conference. Vol. 8, 2010.P. 92−94.

5. Korolenko Ju. A. Heat transfer from a horizontal bundle of pipes to air under conditions of free convection // Izvestiya of the Tomsk Order of the Red Banner of Labor of the Polytechnic Institute named after

6. SM. Kirov 1962. № 110. P. 26−33.

7. Samorodov A. V. Improvement of the method of thermal calculation and design of air cooling units with staggered finned beams: Avtoref dis. kand. tehn. nauk 05.14.14. 1999. P. 3−22.

8. Novozhilova A. V.Analysis of methods for determining the heat transfer of air on finned heating surfaces under free convection //Problems of heatpower engineering in the European North: Sat. Sci. Tr. – Arkhangelsk: Northern (Arctic) Federal University, 2010. – P. 88–97.

9. Martynenko O. G., Sokovishin Ju. A. Free-convective heat transfer: Handbook. - Mn.: Science and Technology, 1982. – 400 p.

10. Novozhilova A. V.To the calculation of the heat exchange of corridor bundles from bimetallic ribbed pipes at different tube angles in the free convection regime // Abstracts and reports of the XV International Forum on Heat and Mass Transfer, Minsk, May 23 – 26, 2016, Minsk, 2016. – P. 157 – 161.

11. Suhockij A. B., Farafontov V. N, Filatov S. O., Sidorik G. S. Development of the stand and investigation of free convection of a single finned tube at different angles of inclination // Proceedings of BSTU. Ser. I. Forestry, nature management and processing of renewable resources – 2017. Vol. I. – Minsk: BSTU, 2017. P. 169 – 175.

12. Sidorik G. S. Experimental installation for investigating the free convection heat exchange of finned tubes of air-cooled heat exchangers // Journal "Polytechnical youth magazine" MSTU im. N.E. BAUMANA. – Moscow: MSTU im. N.E. BAUMANA, 2016. – pp. 1–7.

13. Samorodov A. V. To the calculation of heat transfer by radiation of round-rimmed tubes and bundles, Tr. Forest Engineering Faculty of Petrozavodsk State University. University.1999. V. 2. P. 135−142.


Review

For citations:


Sukhotskii A.B., Sidorik G.S. INVESTIGATION OF A MIXED-CONVECTIVE HEAT TREATMENT OF SINGLEAIR AIR COOLED EXCHANGERS IN VARIOUS CROSS-STEPS PIPE INSTALLATION. Power engineering: research, equipment, technology. 2017;19(11-12):3-11. (In Russ.) https://doi.org/10.30724/1998-9903-2017-19-11-12-3-11

Views: 433


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 1998-9903 (Print)
ISSN 2658-5456 (Online)